This text describes the Acti9 iC60H, a low-voltage installation circuit breaker with dual tunnel connections. It is a 3P installation circuit breaker with 3 protected poles, with a nominal current of 25A and a C cut-off characteristic.
This circuit breaker’s cut-off capacity is 10000A at 400VAC according to the standard EN/IEC 60898-1 (domestic standard) and 30kA at 220VAC to 240VAC according to the standard EN/IEC 60947-2 (industrial standard). This iC60N installation circuit breaker meets both the domestic standard EN/IEC 60898-1 and the industrial standard EN/IEC 60947-2.
It protects power circuits against short circuits and overload currents. The unique VisiTrip indicator shortens the search for the switched-off (tripped) circuit breaker by clearly marking it. The green indication of VisiSafe guarantees the physical opening of the contacts, allowing maintenance to be performed downstream. The rapid cut-off mechanism extends the life of this component.
This Schneider Electric installation circuit breaker has an electrical lifespan up to 10,000 cycles and a mechanical lifespan up to 20,000 cycles. The Ui assigned insulation voltage is 500VAC. Its limitation class 3 (as per EN/IEC60898-1) reduces the costs for protecting the power circuit. It can be mounted on a DIN rail for a modular installation.
The width of this circuit breaker is 3 modules of 18mm. The pollution degree is 3 and the overvoltage category is IV. This product is executed in white color (RAL9003). The dimensions are 54mm (width) x 85mm (height) x 78.5mm (depth). The weight is 0.375kg. The protection degree is IP20 according to the standard IEC 60529. The protection degree increases to IP40 when mounted in a modular enclosure with insulation class II.
The operating temperature is between -35°C and 70°C. The storage temperature is between -40°C and 85°C.
Specifications
Built-in depth (mm) : 44.5
Release characteristic : C
Number of poles (total) : 3
Number of protected poles : 3
Rated current (A) : 25
Rated voltage (V) : 400
Rated insulation voltage Ui (V) : 500
Rated impulse withstand voltage Uimp (kV) : 6
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V (kA) : 10
Voltage-type : AC/DC
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V (kA) : 10
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V (kA) : 30
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V (kA) : 15
Frequency (Hz) : 50 Hz to 60 Hz
Current limiting class : 3
Flush-mounted installation : No
Concurrently switching neutral conductor : No
Over voltage category : 4
Pollution degree : 3
Additional equipment possible : Yes
Width in number of modular spacings : 3
Degree of protection (IP) : IP20
Ambient temperature during operating (°C) : -35 °C to 70 °C
Connectable conductor cross section multi-wired (mm²) : 1 mm² to 16 mm²
Connectable conductor cross section solid-core (mm²) : 1 mm² to 25 mm²
Explosion-proof : No