This text describes the Acti9 iC60H, a low-voltage multi-standard circuit breaker with dual tunnel connections. It is a 2P circuit breaker with two protected poles and has a nominal current of 16A and a C cut-off characteristic. The cut-off capacity of this circuit breaker is 10000A at 400VAC according to the EN/IEC 60898-1 standard (domestic standard), and 30kA at 220VAC to 240VAC according to the EN/IEC 60947-2 standard (industrial standard).
This iC60N circuit breaker complies with both the domestic standard EN/IEC 60898-1 and the industrial standard EN/IEC 60947-2. It protects power circuits from short circuits and overload currents. The unique VisiTrip indicator shortens the search for the switched off (tripped) circuit breaker by clearly marking it. The green indication of VisiSafe ensures the physical opening of the contacts, allowing maintenance to be carried out downstream. The rapid cut-off mechanism extends the life of this component.
This Schneider Electric circuit breaker has an electrical life of up to 10000 cycles and a mechanical life of up to 20000 cycles. The assigned insulation voltage Ui is 500VAC. Its limitation class 3 (according to EN/IEC60898-1) reduces the cost of protecting the power circuit. It can be mounted on a DIN rail for a modular installation. The width of this circuit breaker is 2 modules of 18mm. The pollution degree is 3 and the overvoltage category is IV.
This product is white (RAL9003). The dimensions are 36mm (W) x 85mm (H) x 78.5mm (D). The weight is 0.25kg. According to the IEC 60529 standard, the degree of protection is IP20. The degree of protection increases to IP40 when mounted in a modular enclosure with insulation class II. The operating temperature is between -35°C and 70°C. The storage temperature is between -40°C and 85°C.
Specifications
Built-in depth (mm) : 44.5
Release characteristic : C
Number of poles (total) : 2
Number of protected poles : 2
Rated current (A) : 16
Rated voltage (V) : 400
Rated insulation voltage Ui (V) : 500
Rated impulse withstand voltage Uimp (kV) : 6
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V (kA) : 10
Voltage-type : AC/DC
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V (kA) : 10
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V (kA) : 30
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V (kA) : 15
Frequency (Hz) : 50 Hz to 60 Hz
Current limiting class : 3
Flush-mounted installation : No
Concurrently switching neutral conductor : No
Over voltage category : 4
Pollution degree : 3
Additional equipment possible : Yes
Width in number of modular spacings : 2
Degree of protection (IP) : IP20
Ambient temperature during operating (°C) : -35 °C to 70 °C
Connectable conductor cross section multi-wired (mm²) : 1 mm² to 16 mm²
Connectable conductor cross section solid-core (mm²) : 1 mm² to 25 mm²
Explosion-proof : No