The Acti9 iC60N is a low-voltage circuit breaker. It is a 1P+N circuit breaker with 1 protected pole and a switched neutral. It has a nominal current of 10A and a C cut-off characteristic. This circuit breaker boasts a breaking capacity of 6000A at 230VAC per the EN/IEC 60898-1 standard (domestic standard), and 10kA at 220VAC to 240VAC per the EN/IEC 60947-2 standard (industrial standard). The iC60N circuit breaker complies with both the domestic standard EN/IEC 60898-1 and the industrial standard EN/IEC 60947-2.
This breaker protects power circuits from short-circuits and overload currents. It features a unique VisiTrip indicator which clearly marks the switched off, or tripped, circuit breaker. The VisiSafe green indication guarantees the physical opening of the contacts, allowing for downstream maintenance. The inclusion of a quick cut-off mechanism extends the life of this component.
This Schneider Electric circuit breaker has an electrical lifespan of up to 10,000 cycles and a mechanical lifespan of up to 20,000 cycles. It is assigned an insulation voltage of 500VAC. With a limitation class of 3 (according to EN/IEC60898-1), it reduces the costs for protecting the power circuit. It is mountable on a DIN rail for modular installation.
The breaker is 2 modules wide, with each module measuring 18mm. It has a contamination grade of 3 and an overvoltage category of IV. It is white (RAL9003) in color. The dimensions are 36mm (W) x 85mm (H) x 78.5mm (D) and it weighs 0.25kg.
Per the IEC 60529 standard, the degree of protection it offers is IP20. This degree of protection can increase to IP40 when mounted in a modular housing with insulation class II. The operating temperature range is between -35°C and 70°C, while the storage temperature range is between -40°C and 85°C.
Specifications
Built-in depth (mm) : 44.5
Release characteristic : C
Number of poles (total) : 2
Number of protected poles : 1
Rated current (A) : 10
Rated voltage (V) : 230
Rated insulation voltage Ui (V) : 500
Rated impulse withstand voltage Uimp (kV) : 6
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V (kA) : 6
Voltage-type : AC/DC
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V (kA) : 10
Frequency (Hz) : 50 Hz to 60 Hz
Current limiting class : 3
Flush-mounted installation : No
Concurrently switching neutral conductor : No
Over voltage category : 4
Pollution degree : 3
Additional equipment possible : Yes
Width in number of modular spacings : 2
Degree of protection (IP) : IP20
Ambient temperature during operating (°C) : -35 °C to 70 °C
Connectable conductor cross section multi-wired (mm²) : 1 mm² to 16 mm²
Connectable conductor cross section solid-core (mm²) : 1 mm² to 25 mm²
Explosion-proof : No





Reviews