The Eaton Industries MCCB motor protection switch has a size of 90x88x145mm and an overload setting range of 50-63A. It’s suitable for built-in device construction with fixed installation, offering a nominal continuous current Iu of 63A, and uses a different connection method for the main current circuit. With a thermomagnetic trip technology, this device provides protection up to a level of IP20. Furthermore, it’s part of the NZM…-M series circuit-breakers which are compact and flexible in mounting, designed for the IEC market. They come with thermomagnetic releases for motor protection, display phase-failure sensitivity, and meet all requirements of the AC-3 switching category under the IEC/EN 60947-4-1 and IEC/EN 60947-2 standards.
Specifications
Overload release current setting (A) : 50 A to 63 A
Adjustment range undelayed short-circuit release (A) : 504 A to 882 A
With thermal protection : Yes
Phase failure sensitive : Yes
Switch off technique : Thermomagnetic
Rated operating voltage (V) : 690 V to 690 V
Rated permanent current Iu (A) : 63
Rated operation power at AC-3, 230 V (kW) : 18.5
Rated operation power at AC-3, 400 V (kW) : 30
Type of electrical connection of main circuit : Other
Type of control element : Rocker lever
Device construction : Built-in device fixed built-in technique
With integrated auxiliary switch : No
With integrated under voltage release : No
Number of poles : 3
Rated short-circuit breaking capacity lcu at 400 V, AC (kA) : 35
Degree of protection (IP) : IP20
Height (mm) : 145
Width (mm) : 90
Depth (mm) : 88





Reviews