The Eaton Industries NZM2 Circuit-breaker is a three-pole device with a rated current or uninterrupted current of 160A. It boasts a switching capacity of 25 kA for 600Y/347 V 60 Hz (Icu) and 35 kA for 480 V 60 Hz (Icu). The unit is fixed and connects via screws. The acceptable ranges for overload protection are 125 – 160A, while the undelayed short circuit ranges are 960 – 1600A. This circuit breaker follows UL/CSA and IEC standards, functioning for system and cable protection. Its maximum voltage rating is 690V.
Specifications
Rated permanent current Iu (A) : 160
Rated voltage (V) : 690 V to 690 V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz (kA) : 50
Overload release current setting (A) : 125 A to 160 A
Adjustment range short-term delayed short-circuit release (A) : 0 A to 0 A
Adjustment range undelayed short-circuit release (A) : 960 A to 1600 A
Integrated earth fault protection : No
Type of electrical connection of main circuit : Screw connection
Device construction : Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting : No
DIN rail (top hat rail) mounting optional : Yes
Number of auxiliary contacts as normally closed contact : 0
Number of auxiliary contacts as normally open contact : 0
Number of auxiliary contacts as change-over contact : 0
With switched-off indicator : No
With integrated under voltage release : No
Number of poles : 3
Position of connection for main current circuit : Front side
Type of control element : Rocker lever
Complete device with protection unit : Yes
Motor drive integrated : No
Motor drive optional : Yes
Degree of protection (IP) : IP20